by Regardt Voigt | Feb 9, 2024
The FR-S500 VFD series is discontinued (Legacy). It is being replaced by the FR-D700 VFD series.
by Regardt Voigt | Feb 9, 2024
The FR-A024 series is legacy (discontinued) and is being replaced by the FR-E700 series. (Note also, that the E700 series is also discontinued, and therefore needs to be replaced by the FR-E800 series.)
by Regardt Voigt | Sep 23, 2022
The FR-E800-SCE VSD is a safety VSD therefore it does not have the STR or STF terminals. FR-E800-SCE Terminals Knowledge Base article: Why the FR-E800-SCE does not have STR and STF terminals (mymitsubishisupport.co.za) FR-E800-SCE Instruction Manual (Functional...
by Regardt Voigt | Jul 25, 2022
All FR-E800 inverters have a built-in Safety circuit. Please refer to the following manual for wiring reference: FR-E800 INSTRUCTION MANUAL (CONNECTION) (200V / 400V CLASS)...
by Regardt Voigt | Jun 9, 2021
Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.)
by Regardt Voigt | Jun 5, 2021
Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled.
by Regardt Voigt | Jun 5, 2021
The mini B connector is used for connecting with FR Configurator2. A USB memory device can be connected to the A connector (host) to save parameters or trace data or to copy parameters from one A800/F800 to another A800/F800. Parameters can be copied from one to...
by Regardt Voigt | Jun 5, 2021
For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected.
by Regardt Voigt | Jun 5, 2021
No. Writing is not available when the model is different. Writing the parameter copy file using a USB memory device is available only for the same models. Otherwise, the error “Er.4” is displayed.
by Regardt Voigt | Jun 5, 2021
Yes, it can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited.
by Regardt Voigt | Jun 5, 2021
Yes. the options support it. By connecting the following communication option (built-in circuit board) manufactured and sold by HMS to the FR-A800 series, the FR-A800 can be supported by the communication protocol of the Ethernet IP. HMS model: A8NEIP_2P...
by Regardt Voigt | Jun 5, 2021
The Undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an Undervoltage warning power failure only at the control circuit. Not output an Undervoltage warning when the...
by Regardt Voigt | Jun 5, 2021
If using an inverter with a capacity of 75K or higher, or a motor with a capacity of 75 kW or higher, always select and install the inverter based on the capacity of the motor with a DC reactor.
by Regardt Voigt | Jun 5, 2021
It cannot be connected. When using FR-DU08, connect it to the PU connector.
by Regardt Voigt | Jun 5, 2021
THIS website provides a quick breakdown of what the FREQROL FR-A800 series VFD Drive Inverters are about.
by Regardt Voigt | Jun 5, 2021
THIS guide contains a short summary of the FREQROL series VFD drive inverters available.
by Regardt Voigt | Jun 2, 2021
A VFD (Variable Frequency Drive), also referred to as a VSD (Variable Speed Drive), inverter or drive, is a piece of hardware that is used to control the speed of an AC Induction motor. This is achieved by the VFD controlling the Frequency output (Hz) (in conjunction...
by Regardt Voigt | Jun 2, 2021
Nothing. Both terms are used for describing drive inverters. They are prominently being used interchangeably, depending on the manufacturer of the country. (For Mitsubishi FA, the term VFD is mostly used.). VSD (Variable Speed Drive) refers to the motor shaft...
by Regardt Voigt | Jun 2, 2021
In one word, no. A VFD cannot be used as a replacement for a voltage transformer. If a motor requires 400Vac, then a 400Vac source is required as an input to the 400Vac VFD. The same goes for other voltage classes, The only exception to this rule is with phase number....
by Regardt Voigt | Jun 2, 2021
The FREQROL VFD inverter drive series are available in the following flavors: FR-CS80 – Compact type: Entry-level inverter FR-D700 – Compact type: Compact \ standard FR-E700 \ FR-E800 – Modular type: All-rounder. FR-F800 – Modular type:...