Introduction
Connecting FR-Configurator to the D700 and E700 VSDs is a little different to the F700 and A700 VSDs. This document explains what parameters need to be changed.
Design Considerations
To allow PC control (using FR-Configurator) via the RJ45 port, the following parameters need to be changed in the VSD:
Parameter 122 - needs to be set to 999
Parameter 551 - needs to be set to 4
The details of these settings are shown below.
After the setting of these parameters the VSD will need resetting (power cycle) for the port function to change.
Further Information
For further information see the D700 and E700 manuals and also the FR-Configurator software help.